China · Yongfan Electric Co., Ltd. (YOF®) — ISO9001 & CCC Certified OEM/ODM Manufacturer
Independently developed and manufactured in China by Yongfan Electric Co., Ltd. (YOF®)—an ISO9001 & CCC-certified manufacturer, factory, and global B2B supplier—the Intelligent Soft Starter uses a high-performance microprocessor as its control core. It integrates SCR (thyristor) power drive technology, hardware and software protection, a menu-driven LCD screen, keypad operation, torque control, and a fuzzy PID closed-loop control algorithm into an advanced intelligent motor starting device.
Combining smooth motor soft start, soft stop, light-load energy saving, and comprehensive motor protection functions with stable performance, this series is widely deployed across industrial and commercial transmission equipment, ventilation fans, water pumps, compressors, and heavy loads. All units strictly comply with national and international standards GB14048.6-2008 (and IEC60947-2-2: 2002) and are available for bulk wholesale, custom OEM, and ODM engineering projects.
| Code Segment | Designation | Specification Details |
|---|---|---|
| □□□ | Product Code | Enterprise/series model identifier |
| 55 | Power Rating | Applicable motor rated power (e.g., 55kW) |
| A / B / C / D / E | Structural Configuration | A: Bypass soft starter | B: Bypass soft start cabinet | C: Online soft starter | D: Online soft start cabinet | E: Built-in bypass soft starter |
| T4 / T6 | Power Phase & Voltage | T: Three-phase power supply | 4: 380V | 6: 660V |
| M | Communication Function | Indicates RS485 / serial communication capability |
| Project (Item) | Specification |
|---|---|
| Standards Compliant | GB14048.6 / IEC60947-2-2: 2002 |
| Three-Phase Power | Voltage (AC) 380V ± 15% (220V and 660V Optional) |
| Frequency | 50 / 60Hz |
| Applicable Motor | Squirrel-cage three-phase asynchronous motor |
| Start Frequency | Full-load motor start: no more than 4 times/hour; no-load or light-load: recommended no more than 10 times/hour |
| Degree of Protection | IP20 |
| Shock Resistance (Impact) | Conforms to IEC68-2-27: 15g, 11ms |
| Seismic / Vibration Capacity | Altitude below 3000 meters above sea level, vibration intensity below 0.5g |
| Ambient Temperature | Operating temperature 0~40°C without derating (between +40°C~60°C, derate current by 2% for every 1°C increase) and less than 60°C |
| Storage Temperature | -25°C ~ 70°C |
| Environment Humidity | 93% without condensation or dripping, in compliance with IEC68-2-3 |
| Maximum Operating Altitude | Within 1000 meters altitude without derating (above 1000 meters, derate current by 5% for each additional 100 meters) |
| Cooling Method | Natural air cooling |
| Mounting Orientation (Relative to Vertical) | Vertical installation, tilt angle within ±10° |
| Code | Name | Predetermined Area (Setting Range) | Factory Default | Description |
|---|---|---|---|---|
| F0 | Starting voltage | 30-80% | 30% | Effective in voltage ramp mode; in current limit mode, the starting voltage is fixed at 40% |
| F1 | Soft start time | 2-60S | 16S | Invalid in current limit mode |
| F2 | Soft stop time | 0-60S | 0S | Set to 0 for free stop (coast-to-stop); please set to 0 for one-to-two (dual-motor) drive wiring |
| F3 | Interval delay | 0-999S | 0S | Sets the interval time between starts to prevent equipment damage from frequent starting |
| F4 | Programming delay | 0-999S | 0S | Used for programmable relay output delay |
| F5 | Starting limit current | 50-500% | 280% | Effective in current limit mode; in voltage ramp mode, the maximum current limit is 400% |
| F6 | Maximum operating current | 50-200% | 100% | Percentage of the rated current of the motor |
| F7 | Under-voltage protection | 40-90% | 80% | Protection trips when supply voltage falls below the set value |
| F8 | Overvoltage protection | 100-140% | 120% | Protection trips when supply voltage exceeds the set value |
| F9 | Start mode | 0-5 | 1 | 0: Current limit | 1: Voltage ramp | 2: Kickstart + Current limit | 3: Kickstart + Voltage ramp | 4: Current ramp (slope) | 5: Dual closed-loop |
| FA | Output protection allowed | 0-4 | 4 | 0: Primary | 1: Light load | 2: Standard | 3: Heavy load | 4: Advanced |
| FB | Operation control method | 0-6 | 1 | 0: Keypad | 1: Keypad + External control | 2: External control | 3: External control + Communication | 4: Keypad + External control + Communication | 5: Keypad + Communication | 6: Communication | 7: Start/stop prohibited |
| FC | Parameter modification allowed | 0-2 | 1 | Please refer to the manual for details |
| FD | Communication address | 0-63 | 0 | Used for multi-unit communication between multiple soft starters and a host computer |
| FE | Programming output | 0-19 | 7 | Run relay output (terminals 03, 04) setting |
| FF | Soft stop current limit | 20-100% | 80% | Please refer to the manual for details |
| FP | Motor rated current | — | Rated value | Used to input the nominal rated current of the motor |
| FU | Bypass delay | 1-99S | 5 | Increases the bypass switching delay time |
| FL | Three-phase balance allowed | 0-1 | 1 | 0: Prohibited | 1: Permitted |
| FM | Current coefficient | 50-150% | 100% | Decrease coefficient if displayed current is higher than actual; increase if lower |
| FN | Voltage coefficient | 50-150% | 100% | Decrease coefficient if displayed voltage is higher than actual; increase if lower |
Three-phase AC induction motors are widely used in agriculture, commercial buildings, and industrial plants due to their rugged durability, simple structure, and maintenance-free operation. However, during direct-on-line (DOL) starting, a three-phase AC induction motor draws a severe inrush starting current—typically 6 to 8 times its rated working current (IN)—while generating starting torque and breakdown (pull-out) torque reaching 2 to 4 times its rated torque (MN).
For driven machinery sized according to rated motor torque, direct starting creates severe mechanical shock loads and results in three major engineering drawbacks:
Each phase of the soft starter employs two anti-parallel thyristors (SCRs)—one conducting during the positive half-wave and the other during the negative half-wave. Using phase-angle triggering control within a selectable start-up ramp time, the controller continuously increases the effective RMS motor voltage from a selectable initial starting voltage up to the full rated line voltage. Because motor starting current is directly proportional to the applied voltage, the starting current is reduced linearly by the voltage reduction factor. Meanwhile, because motor torque is proportional to the square of the applied voltage, the starting torque decreases quadratically with voltage reduction—eliminating mechanical shock and current surges.
As a direct China manufacturer and supplier, Yongfan Electric Co., Ltd. (YOF®) supplies ISO9001 & CCC certified intelligent motor soft starters (Bypass Type A/B, Online Type C/D, and Built-In Bypass Type E) for industrial and commercial projects worldwide. Contact our engineering team to request the complete product datasheet, wiring specification manual, flexible MOQ terms, or a competitive factory quote for bulk order and custom OEM/ODM cabinet solutions.